Safe to remove from EF-70?

EM, NEMA, whatever - if it controls a traffic signal, you can talk about it here.

Moderator: SignalLab

Safe to remove from EF-70?

Postby NKS_Signal on Mon Nov 24, 2008 5:00 pm

I would like to remove the filter highlighted in red. Would it be safe to do so? Is it really necessary to have?
Thanks,
Nabil.

Image
NKS_Signal
Crusty Old Salt
Crusty Old Salt
 
Posts: 1155
Joined: Wed Nov 05, 2008 8:35 pm

Re: Safe to remove from EF-70?

Postby RunsWithCrouse-Hinds on Mon Nov 24, 2008 5:15 pm

From what I understand, the filter is totally safe to remove; it looks like a line noise filter, which filters out interference from the AC coil in the controller that causes AM radio static and things like that. However, the question is, why do you want to remove it? Is it causing problems? Removing it may annoy your old neighbors who listen to AM radio I suppose... :talker:

-Dan
Dan B.
Controller and Systems Support Engineer
Econolite Control Products, Inc.
Colorado Springs, CO
User avatar
RunsWithCrouse-Hinds
Crusty Old Salt
Crusty Old Salt
 
Posts: 2282
Joined: Thu Oct 23, 2008 5:10 pm
Location: Colorado Springs, CO

Re: Safe to remove from EF-70?

Postby NKS_Signal on Tue Nov 25, 2008 12:01 pm

Thank you Dan.

I am trying to clean out the controller a bit, getting ready for some use. I will also be breaking the connection between ground and AC. Hopefully I wont get shocked. Image
Nabil.
NKS_Signal
Crusty Old Salt
Crusty Old Salt
 
Posts: 1155
Joined: Wed Nov 05, 2008 8:35 pm

Re: Safe to remove from EF-70?

Postby RunsWithCrouse-Hinds on Tue Nov 25, 2008 1:02 pm

I would say if it is already hooked up like that, it would almost be more work to remove it and remake those connections than it would be to just leave it. Everything should fit around it anyway. What is the little black thing with the ID tag on it on the left? I wonder if maybe that is the interference filter...I've yet to have the opportunity to stick my head into an EF70 so I don't know for sure.

-Dan
Dan B.
Controller and Systems Support Engineer
Econolite Control Products, Inc.
Colorado Springs, CO
User avatar
RunsWithCrouse-Hinds
Crusty Old Salt
Crusty Old Salt
 
Posts: 2282
Joined: Thu Oct 23, 2008 5:10 pm
Location: Colorado Springs, CO

Re: Safe to remove from EF-70?

Postby NKS_Signal on Tue Nov 25, 2008 3:45 pm

What is the little black thing with the ID tag on it on the left?



It's a Mercury relay, seems to be standard equipment on an EF-70 (not an EF-20 though). When activated it makes a loud buzzing sound, so it has since been replaced with a standard relay.
NKS_Signal
Crusty Old Salt
Crusty Old Salt
 
Posts: 1155
Joined: Wed Nov 05, 2008 8:35 pm


Return to Signal Controllers